Fridge guard v1: how it behaves

Step through normal running, the France-style attack, the board tripping and holding, and the board itself failing. Wires carrying current show moving dashes; relay blades show where each contact sits. Temperatures are a chiller example: 8 °C time ceiling, 20 °C instant ceiling. Select any box on the right of the schematic for more on what it is and how the board controls it.

Why the board doesn’t spoof the controller’s sensor

The original idea was to route the case sensor through a resistor network and make the controller think the case was hot, so it would call for cooling itself. It was dropped from v1 for these reasons.

Instead, the board takes the heaters, fans and cooling demand over directly with relays, which works whatever the controller’s settings are.

Watching

Normal operation

Case air, board’s own probe3.2 °C
Animated guard board wiring The guard board between the case controller and the cooling load, evaporator fans and heater contactor. Relay positions and current flow change with the selected step. Case controller Existing, unmodified Cooling out calling Fan out on Defrost out off Sensors S3 / S4 / S5 wired as now Guard board v1 No radio, no network port Watching J2 J3 J4 OC1 mains sense → SENSE_COOL N K1 cooling changeover L_OVR NO NC COM coil ← DRV1 J2 Cooling load Liquid solenoid coil, or compressor contactor coil Cooling N OC2 mains sense → SENSE_FAN N K2 fan changeover L_OVR NO NC COM coil ← DRV2 J3 Evaporator fans Fan motors, or fan contactor coil Running N OC3 mains sense → SENSE_DEF N K3 heater cut NO, unused NC COM coil ← DRV3 J4 Heater contactor coil Defrost heaters switched by the contactor, never via the board Off N K4 alarm, volt-free NO NC COM coil ← DRV4 J5 Store alarm or BMS input K4 energised = healthy Opens on trip or board failure Healthy K0 override master coil ← DRV0 L_OVR Site supply, 230 V Same circuit as the case controller L N PE J1 F1 T500 mA F2 T6.3 A N bus OC1–OC3 returns Enclosure earth PSU 230 V AC → 5 V / 3.3 V Reinforced isolation Watchdog Drops K0 and coil supply if heartbeat stops MCU, no radio e.g. RP2040 or STM32 ADC: own NTC IN: SENSE_COOL / FAN / DEF IN: DIP bank, reset, service key OUT: LEDs, buzzer, heartbeat ULN2003 relay driver → DRV0 – DRV4 J6 Own NTC probe 10 k, in case air-off 3.2 °C Fridge guard, v1 behaviour Concept schematic, not for build Rev B, 5 November 2026

Changes from rev A: the override live is now L_OVR, and it only exists while K0 is closed. K0 is driven by the MCU and dropped by the watchdog, so a hung MCU or a welded K1 or K2 contact can’t leave a load forced on.